CPR references: proven results of heat exchanger cleaning

NPPs, thermal power plants, district heating networks and industrial facilities in Ukraine. No-dismantling chemical hydro-impulse cleaning down to bare metal, documented with acceptance certificates, protocols and before/after endoscopy.
Spiral-wound gas cooling heat exchanger

SERVICE LIFE: 30 years

TYPE: spiral-wound, gas/water

Medium cleaned: service water

Operating pressure: 0.75 MPa

Temperature range (water): 28–50 ℃

Heat exchange area: 6.6 m2

Tube diameter / material: 32×3 / 12Kh18N10T

Tube length: 66 m

Spiral-wound heat exchanger for bearing lube oil bath cooling

SERVICE LIFE: 3 years

TYPE: spiral-wound, oil/water

Medium cleaned: fresh water

Flow rate: 40 l/min

Operating pressure: 15–25 bar

Temperature range (water): max 50 ℃

Tube material: copper alloy + protective coating

PSV-400 district heating water heater

TYPE: shell-and-tube

Medium cleaned: service water

Rated water flow: 400 m3/h

Volume: 425 l

Operating pressure: 0.78 MPa

Number of tubes: 584 (14×1), 08Kh18N10T

Shell length L: 3152 mm

Shell diameter: 630 mm

Heat exchange area: 68 m2

TNG-1200-3000 UKhM

TYPE: shell-and-tube

Medium cleaned: service water (shell side)

Rated water flow: 400 m3/h

Volume: 2020 l

Operating pressure: 0.55 MPa

Number of tubes: 1128 (25×2), 0Kh17N16M3T

Shell length L: 3000 mm

Shell diameter: 1200 mm

Heat exchange area: 266 m2

Condenser of the 2KA60/6S self-contained air conditioner

TYPE: shell-and-tube

Medium cleaned: service water

Rated water flow: 5 m3/h

Volume: 0.16 m3

Operating pressure: 0.6 MPa

Number of tubes: 88

Tube material: L68 brass

Shell length: 800 mm

Shell diameter: 250 mm

Heat exchange area: 0.90 m2

Electric motor air cooler

SERVICE LIFE: 2 years

TYPE: shell-and-tube

Medium cleaned: service water


• Cooling capacity: 147 kW

• Cooling water flow (C.W.): 29 m³/h

• Design pressure: 9 bar

• Tube material: C7060T / C1220T

OGTs heat exchanger

SERVICE LIFE: 35 years

TYPE: shell-and-tube

Rated water flow: 1700 m3/h

Volume: 6.110 m3

Medium: service water

Operating pressure: 0.25 MPa

Temperature range: 24–45 °C

Number of tubes: 3606

Shell length: 5090 mm

Shell diameter: 1900 mm

Heat exchange area: 896 m2

SPIRAL-WOUND WATER-COOLED HEAT EXCHANGERS OF PUMP UNIT LUBE OIL BATHS
INPUT DATA:

Heat exchanger type: SPIRAL-WOUND
Heat exchanger characteristics: - Material: AISI 316L
- Tube 12×1 mm, L = 22 m
- Rated pressure: 3 bar.
Purpose: cooling of the lubricant in the pump oil bath.

Condition of the tube side of the heat exchanger:
1. Inner diameter reduced by 1.5–2.5 mm.
2. Hard deposits 1.5–2.5 mm thick on the inner surface of the coil tubes.

Conclusion:
1. Hard deposits significantly reduce heat transfer performance.
2. The narrowed inner diameters of the coils reduce the coolant flow through the tube side.

WORK PERFORMED

As part of a set of measures to restore the heat exchange and flow-pressure characteristics of the pump heat exchangers on the service water side (tube side), no-dismantling chemical cleaning of the inner surface of the pump coil tubes by the hydro-impulse method was carried out from 01.02.2023 to 03.02.2023.



RESULTS AND CONCLUSIONS

The work using CPR technology cleaned the heat exchange surface. Insoluble particles were removed. The analysis was carried out by endoscopy.

Cleaning of a spiral-wound heat exchanger.
Endoscopy before the work, the cleaning process and endoscopy after cleaning.
SHELL-AND-TUBE FUEL HEATER OF A DIESEL LOCOMOTIVE
INPUT DATA:


Unit: fuel heater of the K6S310DR diesel engine (ChME3 locomotive)
Type: tubular heat exchanger, water inside the tubes / fuel on the shell side.
Shell: cylindrical steel, with two tube sheets.
Tubes:
  • Material: copper
  • Quantity: 123
  • Size: 11×0.5 mm (outer diameter × wall thickness).
Working media:
  • Inside the tubes: diesel cooling system water, up to 85 °C.
  • On the shell side: diesel fuel at a pressure of about 2.0 kgf/cm².




RESULTS AND CONCLUSIONS

The work using CPR technology cleaned the heat exchange surface. Insoluble particles were removed. The analysis was carried out by endoscopy.

Cleaning of the fuel heater.
Endoscopy before the work, the cleaning process and endoscopy after cleaning.